The following tables give the RAM addresses and the parameter calculation units that the machine uses for ringing signal detection and automatic dialing. The factory settings for each country are also given. Most of these must be changed by RAM read/write (SP2-102), but some can be changed using NCU Parameter programming (SP2-103); if SP2-103 can be used, this will be indicated in the Remarks column. The RAM is programmed in hex code unless (BCD) is included in the Unit column.

  • The following addresses describe settings for the standard NCU.

AddressFunctionUnitRemarks
7EB52000Country/Area code for NCU parameters Use the Hex value to program the country/area code directly into this address, or use the decimal value to program it using SP2-103-001
7EB520B4PSTN: TX level from the modem-N – 3 dBmSP2-103-002 (parameter 01).
7EB52072Acceptable ringing signal frequency: range 1, upper limit1000/ N (Hz)SP2-103-003 (parameter 02).
7EB52073Acceptable ringing signal frequency: range 1, lower limit1000/ N (Hz)SP2-103-004 (parameter 03).
7EB52074Acceptable ringing signal frequency: range 2, upper limit1000/ N (Hz)SP2-103-005 (parameter 04).
7EB52075Acceptable ringing signal frequency: range 2, lower limit1000/ N (Hz)SP2-103-006 (parameter 05).
7EB52076Number of rings until a call is detectedtime(s)SP2-103-007 (parameter 06).
The setting must not be zero.
7EB52077Minimum required length of the first ringN x 20msSee Note 2.
SP2-103-008 (parameter 07).
7EB52078Minimum required length of the second and subsequent ringsN x 20msSP2-103-009 (parameter 08).
7EB52079Ringing signal detection reset time (LOW)N x 20msSP2-103-010 (parameter 09).
7EB5207ARinging signal detection reset time (HIGH)N x 20msSP2-103-011 (parameter 10).
7EB5204ADo not change the settings.  
7EB5204BBreak time for pulse dialingmsSee Note 1.
SP2-103-013 (parameter 12).
7EB5204CMake time for pulse dialingmsSee Note 1.
SP2-103-014 (parameter 13).
7EB5204DDo not change the settings.  
7EB5204EMinimum pause between dialed digits (pulse dial mode)N x 20msSee Note 1 and 4. SP2-103-016 (parameter 15).
7EB5204FTime waited when a pause isentered at the operation panelN x 20msSP2-103-017 (parameter 16).
See Note 1.
7EB52050DTMF tone on timemsSP2-103-018 (parameter 17).
7EB52051DTMF tone off timemsSP2-103-019 (parameter 18).
7EB52052Tone attenuation level of DTMF signals while dialingdBm
(See Note 5)
SP2-103-020 (parameter 19).
See Note 3.
7EB52053Tone attenuation value difference between high frequency tone and low frequency tone in DTMF signalsdBm
(See Note 5)
SP2-103-021 (parameter 20).
The setting must be less than – 5dBm, and should not exceed the setting at 7EB52052h above.
See Note 3.
7EB52054Do not change the settings.- 
7EB52055Do not change the settings.- 
7EB971E8 to 7EB973E7Error code storage- 
7EB93800 to 7EB96517Communication history storage- 
7EB973E8 to 7EB982E7Communication error storage- 

NOTES

  1. Pulse dial parameters (addresses 7EB5204A to 7EB5204F) are the values for 10 pps. If 20 pps is used, the machine automatically compensates.
  2. The first ring may not be detected until 1 to 2.5 wavelengths after the time specified by this parameter.
  3. The calculated level must be between 0 and 10.
    The attenuation levels calculated from RAM data are:
    High frequency tone:
    • – 0.5 x N7EB52052/7EB52054–3.5 dBm
    • – 0.5 x N7EB52055 dBm
    Low frequency tone:
    • – 0.5 x (N7EB52052/7EB52054 + N7EB52053) –3.5 dBm
    • – 0.5 x (N7EB52055 + N7EB52053) dBm

      • N7EB52052, for example, means the value stored in address 7EB52052(H)

  4. 7EB5204A, 7EB5204D, 7EB5204E: The actual inter-digit pause (pulse dial mode) is the sum of the period specified by the RAM addresses 7EB5204A, 7EB5204D, and 7EB5204E.